Well Pump Won't Shut Off: The Gauge Test Settles It
The opposite complaint from a short-cycling pump: this one starts and never stops. Both pages are read from the University of Nebraska–Lincoln Extension’s private-well series — this one from Operation and Maintenance for Mechanical Components (G2153, Hygnstrom, Woldt & Skipton; accessed 2026-11-21).
UNL’s two suspects
A continuously running pump, per the source, means either a check valve stuck open (in the pump or the riser pipe) or a break in the water line — between well and building, or inside the building’s plumbing. UNL adds the yard clue directly: a soggy area that isn’t the septic drainfield can mark a buried line break.
The test that sorts them, from the source
Many systems give no outward sign the pump is even running, so UNL’s diagnostic is the one to run first: shut off water to the house and watch the pressure gauge on the tank. If the gauge holds steady, the check valves are working and the lines don’t leak. If the pressure drops, there’s a leak in the line to the house or a failing check valve — either way, a licensed professional’s problem to pinpoint, but now the conversation starts with evidence instead of a guess.
The related complaints on the same tree
G2153’s troubleshooting section covers the neighbors of this problem, worth knowing before assuming the worst:
- No water at all: check house power first, then the well pump’s breaker or fuse — the source puts electricity ahead of everything.
- Little water, especially in heavy use or drought: the pump may sit too high in the well as the water level drops; setting it against the measured static and pumping levels is professional work.
- Pump runs a few seconds and quits: pressure is building too fast because the tank’s air charge is low — that is the short-cycling page’s territory, and UNL’s precharge spec lives there.
Why running-on costs more than it seems
The pressure tank exists so the pump starts and stops less often — UNL’s series is explicit that this prolongs pump life and that starting draws more energy than running. A pump that never shuts off has lost that protection entirely, and every hour adds wear plus the water bill of a possible underground leak. No products are linked on this page; the supply equipment layer arrives only with verified listings, and a stuck check valve or buried break is contractor work regardless.